© National Instruments Corp. 11 FP-PWM-520 and cFP-PWM-520
number or product line, and click the appropriate link in
the Certification column.
Caution Do not disconnect I/O-side wires or connectors
unless power has been switched off or the area is known
to be nonhazardous.
Caution Do not remove modules unless power has been
switched off or the area is known to be nonhazardous.
Caution Substitution of components may impair
suitability for Class I, Division 2.
Caution For Zone 2 applications, install the Compact
FieldPoint system in an enclosure rated to at least IP 54
as defined by IEC 60529 and EN 60529.
Caution For Zone 2 applications, install a protection
device across the external power supply and the COM
terminal. The device must prevent the external power
supply voltage from exceeding 42 V if there is a transient
overvoltage condition.
Special Conditions for Hazardous Locations Use in Europe
The cFP-PWM-520 has been evaluated as EEx nC IIC T4
equipment under DEMKO Certificate No. 03 ATEX 0251502X.
Each module is marked II 3G and is suitable for use in Zone 2
hazardous locations.
Specifications
The following specifications are typical for a range of –40 to 70 °C
unless otherwise noted.
Output Characteristics
Number of channels .......................... 8
Output type ....................................... Sourcing
Output voltage .................................. Supply voltage – (Output
current × Output impedance)
Supply voltage .................................. 5 VDC or 10 to 30 VDC,
user-provided